3. Instruction Set
3-113
Y0
ANS T0 K100 S912
X2
X4
ANRP
M1000
M1049
Y1
ANS T1 K200 S920
X3
X0
Y0
X2
M1048
Y2
Y0
X1
Y1
X3
Y1
1. M1048 and D1049 are valid only when M1049 = ON.
2. When Y0 = ON for more than 10 sec and the product fails to reach the front position X2,
S912 = ON
3. When Y1 = ON for more than 10 sec and the product fails to reach the back position X3,
S920= ON.
4. When backward switch X1 = ON and backward device Y1 = ON, Y1 will go OFF only when
the product reaches the back position switch X3.
5. Y2 is ON when any alarm is enabled.
6. Whenever X4 is ON, 1 active alarm will be reset. If there are several active alarms, the reset
will start from the alarm with the lowest number and then the alarm with second lower
number, etc.