Delta D25886 Manual do Utilizador Página 38

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 37
3. System Installation
DVP-MC operating manual 3-5
The relevant circuit for wiring is shown as figure 3.2.5
Figure 3.2.5
Wiring of output circuit
The circuit plate for the transistor output in DVP10MC11T includes the diodes with the protection function of
counter potential. It is sufficient for application of the inductive load at low power and little higher frequency of
On/Off change. In the case of high power or high On/Off change frequency, please additionally connect the
suppression circuit according to the following figure to decrease the interference and prevent over-voltage or
over-heat from damaging the transistor output circuit.
Figure 3.2.6
24V direct current power
Fuse protector for power circuit protection;
Emergent stop button;
Loading for switch, inductance and etc.
9V Zener diode, 5W;
When the power for loading is quite high and On/Off status is switched frequently, and will be used
together.
Diode or the equivalent object is used as the diode suppressor. When the power for loading is low,
is in no need for use but .