Caution
Connection to electricity supply
The air-conditioning unit must be wired by a trained, qualified electrician in
accordance with the applicable regulations (VDE, local power utility, etc.).
If the intake fan or discharge fan is switched off or fails, all control valves
must close automatically and the hot-water/cold-water and washer pumps
must shut down.
Install only control valves which are closed when de-energized and a frost-
protection thermostat without restart disabler.
Install a lockable repair switch for each drive motor to ensure that the air-
conditioning unit can be reliably shut down.
Completion of the electrical wiring work must be followed by a safety inspection
of the installation in accordance with VDE 0701 Part 1 and VDE 0700 Part 500 or
comparable national safety codes.
Use only electric motors designed to drive fans.
Always comply with the wiring diagram in the terminal box.
Use a thermistor-type trigger for a motor with PTC thermistor, an interlock
contactor for a motor with thermo-contacts, or a thermal overcurrent relay for a
motor without PTC thermistor or therm-contacts.
Connection to electricity
supply
5-stage control
1 unit: Switch: E5-3
2 units parallel: Switch: E5-7
Switch type E5-3 E5-7
Voltage 230V 230V
Current max. 3A 7A
Weight 4.7 kg 8.5 kg
Protection IP 40 IP40
5-stage control
1 unit: Switch: E5-7T
2 units parallel: Switch: E5-14T
Switch type E5-7T E5-14T
Voltage 230V 230V
Current max. 7A 14A
Weight 8.5 kg 12.5 kg
Protection IP 40 IP20
KG 15 KG 20
Mains
230V~
Mains
230V~
Fan
Fan with
thermo-contact
*Remove jumper if a room thermostat is connected
* Remove jumper if a room thermostat is connected
H1 = Operation
H2 = Fault