4.2.3 In-line Installation, Externally Bypassed
Non-bypassed models have dedicated bypass terminals, which allow the soft starter to continue providing protection and
monitoring functions even when bypassed via external contactor. The bypass contactor must be connected to the bypass
terminals and controlled by a programmable output configured to Run (see par. 4.1 - 4.9).
177 HA4 31.11
M
3
F1
6/T3
2/T1
5/L3
3/L2
1/L1
13
14
4/T2
E
KM1
KM1
L1B
L2B
L3B
KM2
34
33
KM2
KM1 Main contactor
KM2 Bypass contactor
F1 Fuses (optional)
N
NOTE
The bypass terminals on MCD5-0245C are T1B, T2B, T3B. The
bypass terminals on MCD5-0360C ~ MCD5-1600C
are L1B,
L2B, L3B.
The fuses can be installed on the input side if required.
4.3 Inside Delta Installation
CAUTION
When connecting the MCD 500 in inside delta configuration,
always install a main contactor or shunt tr
ip circuit breaker.
NOTE
When connecting in inside delta, enter the motor full load
current (FLC) for par. 2-1 Phase Sequence.
MCD 500 software
calculates inside delta currents from this. Par. 15-7 Motor
Connection is set to Auto
detect as default and can be set to
force the soft starter inside delta or in-line.
Electrical Installation MCD 500 Operating Instruction
14 MG.17.K3.02 - VLT
®
is a registered Danfoss trademark