7.7 Outputs
4
4-1 Relay A Function
Option: Function:
Selects the function of Relay A (normally open).
Off Relay A is not used
Main Contactor
The relay closes when the MCD 500 receives a
start command, and remains closed as long as
the motor is receiving voltage.
Run The relay closes when the starter changes to
run state.
Trip The relay closes when the starter trips.
Warning The relay closes when the starter issues a
warning.
Low Current
Flag
The relay closes when the low current flag
activates (Par. 4-10 Low Current Flag).
High Current
Flag
The relay closes when the high current flag
activates (Par. 4-11 High Current Flag).
Motor Temp
Flag
The relay closes when the motor temperature
flag activates (Par. 4-12 Motor Temperature
Flag).
7.7.1 Relay A Delays
The MCD 500 can be configured to wait before opening or
closing Relay A.
4-2 Relay A On Delay
Range: Function:
0 secs* [0:00 - 5:00 (min:secs)] Sets the delay for closing Relay
A.
4-3 Relay A Off Delay
Range: Function:
0 secs* [0:00 - 5:00 (min:secs)] Sets the delay for re-opening
Relay A.
7.7.2 Relays B and C
Parameters 4-4 to 4-9 configure the operation of Relays B
and C in the same way as parameters 4-1 to 4-3 configure
Relay A.
4-4 Relay B Function
Option: Function:
Selects the function of Relay B (changeover).
Off Relay B is not used
Main Contactor The relay closes when the MCD 500 receives a
start command, and remains closed as long as
the motor is receiving voltage.
Run
The relay closes when the starter changes to run
state.
Trip The relay closes when the starter trips.
Warning The relay closes when the starter issues a
warning.
4-4 Relay B Function
Option: Function:
Low Current
Flag
The relay closes when the low current flag
activates (Par. 4-10 Low Current Flag).
High Current
Flag
The relay closes when the high current flag
activates (Par. 4-11 High Current Flag).
Motor Temp
Flag
The relay closes when the motor temperature
flag activates (Par. 4-12 Motor Temperature Flag).
4-5 Relay B On Delay
Range: Function:
0 secs* [0:00 - 5:00 (min:secs)] Sets the delay for closing Relay
B.
4-6 Relay B Off Delay
Range: Function:
0 secs* [0:00 - 5:00 (min:secs)] Sets the delay for re-opening
Relay B.
4-7 Relay C Function
Option: Function:
Selects the function of Relay C (normally open).
Off Relay C is not used
Main Contactor The relay closes when the MCD 500 receives a
start command, and remains closed as long as
the motor is receiving voltage.
Run The relay closes when the starter changes to
run state.
Trip
The relay closes when the starter trips.
Warning The relay closes when the starter issues a
warning.
Low Current
Flag
The relay closes when the low current flag
activates (Par. 4-10 Low Current Flag).
High Current
Flag
The relay closes when the high current flag
activates (Par. 4-11 High Current Flag).
Motor Temp
Flag
The relay closes when the motor temperature
flag activates (Par. 4-12 Motor Temperature
Flag).
4-8 Relay C On Delay
Range: Function:
0 secs* [0:00 - 5:00 (min:secs)] Sets the delay for closing Relay
C.
4-9 Relay C Off Delay
Range: Function:
0 secs* [0:00 - 5:00 (min:secs)] Sets the delay for re-opening
Relay C.
7.7.3 Low Current Flag and High Current
Flag
The MCD 500 has low and high current flags to give early
warning of abnormal operation. The current flags can be
configured to indicate an abnormal current level during
operation, between the normal operating level and the
Programming MCD 500 Operating Instruction
MG.17.K3.02 - VLT
®
is a registered Danfoss trademark 55