T
To use the protection simulation:
1. Open the Main Menu.
2. Scroll to Protection Sim and press O
.
3.
Use the
Ⴃ
and
Ⴍ
buttons to select the protection
you want to simulate.
4. Press O
to simulate the selected protection.
5. The protection message is displayed while O
is
pressed. The soft starter's response depends on the
Protection Action setting (parameter group 16).
6. Press B
to return to the simulation list.
7.
Use
Ⴃ
or
Ⴍ
to select another simulation, or press
to return to the Main Menu.
MS1 000.0A 0000.0kW
Tripped
Selected Protection
NOTE
If the protection trips the soft starter, reset before simulating
another protection. If the protectio
n action is set to 'Warn or
Log', no reset is required.
If the protection is set to 'Warn & Log', the w
arning message
can be viewed only while the 'OK' button is pressed.
If the protection is set to 'Log on
ly', nothing appears on the
screen but an entry will appear in the log.
8.5 Output Signal Simulation
NOTE
This function is protected by the security access code.
The LCP allows the user to simulate output signalling in
order to confirm that the output relays are operating
correctly.
NOTE
To test operation of the flags (motor temperature and low/
high current), set an output relay to the a
ppropriate function
and monitor the relay's behaviour.
To use the output signal simulation:
1. Open the Main Menu.
2. Scroll to Output Signal Sim and press O
, then
enter the access code.
3.
Use the
Ⴃ
and
Ⴍ
buttons to select a simulation,
then press O
.
4.
Use the
Ⴃ
and
Ⴍ
buttons to turn the signal on and
off. To confirm correct operation, monitor the state
of the output.
5. Press B
to return to the simulation list.
Prog Relay A
Off
On
8.6 Digital I/O State
This screen shows the current status of the Digital I/O in
order.
The top line of the screen shows the start, stop, reset and programmable input.
The bottom line of the screen shows programmable outputs
A, B and C.
The screen shot shows the stop input (17) as closed (1) and
the start, reset and Input A inputs (15, 25, 11) as open (0).
Relay A (13, 14) is closed and relays B and C (21, 22, 24 and
33, 34) are open,
Digital I/O State
Inputs: 0100
Outputs: 100
8.7 Temp Sensors State
This screen shows the state of the motor thermistor.
The screen shot shows the thermistor state as O (open).
Temp Sensors State
Thermistor: O
S = shrt H=hot C=cld O=opn
8.8 Alarm Log
The A
button opens the Alarm Logs, which contains
a Trip Log, Event Log, and Counters which store information
on the MCD 500's operating history.
8.8.1 Trip Log
The Trip Log stores details of the eight most recent trips,
including the date and time the trip happened. Trip 1 is the
most recent and trip 8 is the oldest stored trip.
Tools MCD 500 Operating Instruction
MG.17.K3.02 - VLT
®
is a registered Danfoss trademark 63