4.5 Minimum and Maximum Current Settings
The MCD 500's minimum and maximum full load current settings depend on the model:
I
In-line Connection Inside Delta Connection
Model Minimum Maximum Minimum Maximum
MCD5-0021B 5 A 23 A 7 A 34 A
MCD5-0037B 9 A 43 A 13 A 64 A
MCD5-0043B 10 A 50 A 15 A 75 A
MCD5-0053B 11 A 53 A 16 A 79 A
MCD5-0068B 15 A 76 A 23 A 114 A
MCD5-0084B 19 A 97 A 29 A 145 A
MCD5-0089B 20 A 100 A 30 A 150 A
MCD5-0105B 21 A 105 A 32 A 157 A
MCD5-0131B 29 A 145 A 44 A 217 A
MCD5-0141B 34 A 170 A 51 A 255 A
MCD5-0195B 40 A 200 A 60 A 300 A
MCD5-0215B 44 A 220 A 66 A 330 A
MCD5-0245C 51 A 255 A 77 A 382 A
MCD5-0360C 72 A 360 A 108 A 540 A
MCD5-0380C 76 A 380 A 114 A 570 A
MCD5-0428C 86 A 430 A 129 A 645 A
MCD5-0595C 124 A 620 A 186 A 930 A
MCD5-0619C 130 A 650 A 195 A 975 A
MCD5-0790C 158 A 790 A 237 A 1185 A
MCD5-0927C 186 A 930 A 279 A 1395 A
MCD5-1200C 240 A 1200 A 360 A 1800 A
MCD5-1410C 282 A 1410 A 423 A 2115 A
MCD5-1600C 320 A 1600 A 480 A 2400 A
4.6 Bypass Contactor
MCD 500 soft starters with model numbers MCD5-0021B - MCD5-0215B are internally bypassed and do not require an external
bypass contactor.
MCD 500 soft starters with model numbers MCD5-0245C - MCD5-1600C are not internally bypassed and may be installed with
an external bypass contactor. Select a contactor with an AC1 rating greater than or equal to the full load current rating of the
connected motor.
4.7 Main Contactor
A main contactor must be installed if the MCD 500 is connected to the motor in inside delta format and is optional for in-line
connection. Select a contactor with an AC3 rating greater than or equal to the full load current rating of the connected motor.
4.8 Circuit Breaker
A shunt trip circuit breaker may be used instead of a main contactor to isolate the motor circuit in the event of a soft starter trip.
The shunt trip mechanism must be powered from the supply side of the circuit breaker or from a separate control supply.
4.9 Power Factor Correction
If power factor correction is used, a dedicated contactor should be used to switch in the capacitors. Power factor correction
capacitors must be connected to the input side of the soft starter.
Electrical Installation MCD 500 Operating Instruction
MG.17.K3.02 - VLT
®
is a registered Danfoss trademark 21