Storage temperature - 25° C to + 60° C
Operating Altitude 0 - 1000 m, above 1000 m with derating
Humidity 5% to 95% Relative Humidity
Pollution degree Pollution Degree 3
Heat Dissipation
During start 4.5 watts per ampere
During run
MCD5-0021B - MCD5-0053B = 39 watts approx
MCD5-0068B - MCD5-0105B = 51 watts approx
MCD5-0131B - MCD5-0215B = 120 watts approx
MCD5-0245C - MCD5-0927C 4.5 watts per ampere approx
MCD5-1200C - MCD5-1600C 4.5 watts per ampere approx
Certification
C IEC 60947-4-2
UL/ C-UL UL 508
CE IEC 60947-4-2
CCC GB 14048-6
Marine
(MCD5-0021B - MCD5-0215B only) Lloyds Marine No 1 Specification
RoHS Compliant with EU Directive 2002/95/EC
10.1 Accessories
10.1.1 Communication Modules
MCD 500 soft starters support network communication using the Profibus, DeviceNet and Modbus RTU protocols, via an easy-
to-install communications module. The communications module plugs directly onto the side of the starter.
175G9000 Modbus Module
175G9001 Profibus Module
175G9002 DeviceNet Module
175G9009 MCD USB Module
Specifications MCD 500 Operating Instruction
MG.17.K3.02 - VLT
®