1
1
Four-line display for status and programming details.
2
Display control buttons:
S
Status
: Return to the status displays
Quick Menu
: Open the Quick Menu
Main Menu
: Open the Main Menu
Alarm Log
: Open the Alarm Log
3
Menu navigation buttons:
B
BACK
: Exit the menu or parameter, or cancel a
parameter change
OK
: Enter a menu or parameter, or save a parameter
change
: Scroll to the next or previous menu or parameter,
change the setting of the current parameter or scroll
through the status screens.
4
Soft starter local control buttons:
H
Hand On
: Start the motor and enter local control mode.
Off
: Stop the motor (only active in Hand On mode).
Auto On
: Set the starter to Auto On mode.
RESET
: Reset a trip (Hand On mode only).
5
Remote input status LEDs.
6.2 Control Methods
The MCD 500 can be controlled via the control buttons on
the LCP (local control), via the remote inputs (remote
control) or via the serial communication network.
Local control is only available in Hand On mode.
Remote control is only available in Auto On mode.
Control via the serial communication network is
always disabled in Hand On mode, and Start/Stop
commands via the serial network may be enabled
or disabled in Auto On mode by changing the
setting of Par. 3-2 Comms in Remote.
The MCD 500 can also be configured to auto-start or auto-
stop. Auto-start/stop operation is only available in Auto On
mode, and must be configured using pars. 5-1 - 5-4. In Hand
On mode, the starter will ignore any auto-start/stop setting.
To switch between Hand On and Auto On modes, use the
local control buttons on the LCP.
HAND ON
: Start the motor and enter Hand On mode.
OFF
: Stop the motor and enter Hand On mode.
AUTO ON
: Set the starter to Auto On mode.
RESET
: Reset a trip (Hand On mode only).
The MCD 500 can also be set to allow local control only or
remote control only, using par. 3-1 Local/Remote.
If par. 3-1 is set to Remote Control Only, the OFF button is
disabled and the motor must be stopped by remote control
or via the serial communication network.
H
Hand On mode Auto On mode
To soft start the motor press the HAND ON button on the LCP activate the Start remote input
To stop the motor press the OFF button on the LCP activate the Stop remote input
To reset a trip on the starter press the RESET button on the LCP activate the Reset remote input
Auto start/stop operation Disabled Enabled
To emergency stop the motor, press the local OFF and RESET buttons at the same time. The soft starter will remove power from
the motor and open the main contactor, and the motor will coast to stop. Emergency stop can also be controlled via a
programmable input.
NOTE
Brake and Jog functions operate only with in-line connected
motors (see Inside Delta Operation)
6.3 Local Control Buttons
If Par. 3-1 is set to LCL/RMT Anytime or LCL/RMT When OFF,
the H
Hand On
and A
Auto On
buttons are always active. If the
MCD-500 is in Auto On mode, pressing the H
Hand On
button
will enter Hand On mode and start the motor.
If Par. 3-1 is set to Remote Control Only, the O
Off
button is
disabled and the motor must be stopped by remote control
or via the serial communication network.
Operation MCD 500 Operating Instruction
MG.17.K3.02 - VLT
®
is a registered Danfoss trademark 43
6 6