2-4 Undercurrent
Range: Function:
20%* [0% -
100%]
Sets the trip point for undercurrent protection,
as a percentage of motor full load current. Set to
a level between the motor's normal working
range and the motor's magnetising (no load)
current (typically 25% to 35% of full load
current). A setting of 0% disables undercurrent
protection.
2-5 Undercurrent Delay
Range: Function:
5 secs* [0:00 - 4:00
(min:secs)]
Slows the MCD 500's response to
undercurrent, avoiding trips due to
momentary fluctuations.
7.5.3 Instantaneous Overcurrent
The MCD 500 can be configured to trip if the average current
of all three phases exceeds a specified level while the motor
is running.
2-6 Instantaneous Overcurrent
Range: Function:
400%* [80% - 600%
FLC]
Sets the trip point for instantaneous
overcurrent protection, as a percentage
of motor full load current.
2-7 Instantaneous Overcurrent Delay
Range: Function:
0 secs* [0:00 - 1:00
(min:secs)]
Slows the MCD 500's response to
overcurrent, avoiding trips due to
momentary overcurrent events.
7.5.4 Frequency Trip
The MCD 500 monitors mains frequency throughout
operation, and can be configured to trip is the frequency
varies beyond a specified tolerance.
2-8 Frequency Check
Option: Function:
Do not Check
Start Only
Start/Run
Run Only
Determines when the starter will monitor for a
frequency trip.
2-9 Frequency Variation
Option: Function:
Selects the soft starter's tolerance for frequency
variation.
Running a motor outside its specified frequency for
long periods can cause damage and premature failure.
s 2 Hz
2-9 Frequency Variation
Option: Function:
s 5 Hz
s 10 Hz
s 15 Hz
2-10 Frequency Delay
Range: Function:
1 sec* [0:01 - 4:00
(min:sec)]
Slows the MCD 500's response to
frequency disturbances, avoiding trips
due to momentary fluctuations.
NOTE
If the mains frequency drops below
35 Hz or rises above 75 Hz, the
starter will trip immediately.
2-11 Restart Delay
Range: Function:
10
secs*
[00:01 - 60:00
(min:secs)]
The MCD 500 can be configured to force a
delay between the end of a stop and the
beginning of the next start. During the
restart delay, the display shows the time
remaining before another start can be
attempted.
NOTE
The restart delay is measured from
the end of each stop. Changes to the
restart delay setting take effe
ct
immediately.
2-12 Motor Temperature Check
Option: Function:
Selects whether the MCD 500 will verify the motor
has sufficient thermal capacity for a successful
start. The soft starter compares the motor's
calculated temperature with the temperature rise
from the last motor start and only operates if the
motor is cool enough to start successfully.
Do not
Check
Check
7.6 Inputs
3-1 Local/Remote
Option: Function:
Selects when the A
AUTO ON
and H
HAND ON
buttons can be used to switch to Hand On or
Auto On modes.
Lcl/Rmt
anytime
The user can change between local and
remote control at any time.
Local Control
Only
All remote inputs are disabled.
Remote Control
Only
Selects whether the starter can be used in
Hand On or Auto On modes.
Programming MCD 500 Operating Instruction
MG.17.K3.02 - VLT
®
is a registered Danfoss trademark 53