4.4.5 Inside Delta Connection (Bypassed)
N
NOTE
Models MCD5-0021B a MCD5-0215B are internally bypassed.
Models MCD5-0245C a MCD5-1600C require an exte
rnal
bypass contactor.
A
AC-53b
3-30:330
AC-53b
4.20-:340
AC-53b
4.5-30:330
MCD5-0021B 32 A 26 A 22 A
MCD5-0037B 56 A 47 A 39 A
MCD5-0043B 65 A 56 A 45 A
MCD5-0053B 80 A 69 A 55 A
A
AC-53b
3-30:570
AC-53b
4-20:580
AC-53b
4.5-30:570
MCD5-0068B 102 A 83 A 71 A
MCD5-0084B 126 A 104 A 87 A
MCD5-0089B 134 A 112 A 92 A
MCD5-0105B 158 A 143 A 117 A
MCD5-0131B 197 A 159 A 136 A
MCD5-0141B 212 A 181 A 146 A
MCD5-0195B 293 A 241 A 201 A
MCD5-0215B 323 A 268 A 223 A
MCD5-0245C 383 A 302 A 264 A
MCD5-0360C 540 A 465 A 395 A
MCD5-0380C 570 A 539 A 449 A
MCD5-0428C 645 A 552 A 463 A
MCD5-0595C 930 A 810 A 651 A
MCD5-0619C 975 A 842 A 683 A
MCD5-0790C 1185 A 1072 A 869 A
MCD5-0927C 1395 A 1244 A 992 A
MCD5-1200C 1800 A 1800 A 1607 A
MCD5-1410C 2115 A 1979 A 1671 A
MCD5-1600C 2400 A 2400 A 2030 A
4.4.6 AC-53 Rating for Bypassed Operation
All ratings are calculated at altitude of 1000 metres and ambient temperature of 40r C.
Electrical Installation MCD 500 Operating Instruction
MG.17.K3.02 - VLT
®
is a registered Danfoss trademark 19