S
AAC adaptive acceleration control, DC brake
and Jog functions not working
These features are only available with in-line installation. If the MCD 500 is installed inside
delta, these features will not operate.
A reset does not occur after an Auto-Reset,
when using a remote 2-wire control.
The remote 2-wire start signal must be removed and reapplied for a re-start.
Remote start/stop command is overriding Auto
Start/Stop settings when using remote 2-wire
control.
Auto Start/Stop function should only be used in HAND ON mode or in tandem with
HAND OFF mode, 3 and 4-wire control.
After selecting AAC the motor used an ordinary
start and/or the second start was different to
the first.
The first AAC start is current limit so that the starter can learn from the motor character-
istics. Subsequent starts use AAC.
Non-resettable THERMISTOR CCT trip, when
there is a link between Thermistor input 05, 06
or when the motor thermistor connected
between 05, 06 is permanently removed.
The thermistor input is enabled once a link is fitted and short circuit protection has
activated.
Remove the link then load the default parameter set. This will disable the thermistor input
and clear the trip.
Place a 1k2 ˖ resistor across the thermistor input.
Turn thermistor protection to 'Log only' (Par. 16-9).
Parameter settings cannot be stored. -
Make sure you are saving the new value by pressing the O
button after adjusting a
parameter setting. If you press B
, the change will not be saved.
Check that the adjustment lock (Par. 15-2) is set to Read/Write. If the adjustment lock is
on, settings can be viewed but not changed. You need to know the security access code
to change the adjustment lock setting.
The EEPROM may be faulty on the Main Control PCB. A faulty EEPROM will also trip the
soft starter, and the LCP will display the message Par. Out of Range. Contact your local
supplier for advice.
Troubleshooting MCD 500 Operating Instruction
MG.17.K3.02 - VLT
®
is a registered Danfoss trademark 69
Comentários a estes Manuais