1-11 Stop Time
Range: Function:
0 secs* [0:00 - 4:00
(min:secs)]
Sets the time for soft stopping the motor
using timed voltage ramp or Adaptive
Control (AAC). If a main contactor is
installed, the contactor must remain closed
until the end of the stop time. Use a
programmable output configured to Run
to control the main contactor. Sets the toal
stopping time when using brake. See
Stopping Modes in chapter Application
Examples for more details.
1-12 Adaptive Control Gain
Range: Function:
75%* [1% -
200%]
Adjusts the performance of AAC adaptive
acceleration control. This setting affects both
starting and stopping control.
NOTE
We recommend leaving the gain setting at
the default level unless AAC performance
is not satisfactory.
If the motor accelerates
or decelerates quickly at the end of a start
or stop, increase the gain settin
g by
5%~10%. If the motor speed fluctuates
during starting or stopping, decrease the
gain setting slight
ly.
1-13 Adaptive Start Profile
Option: Function:
Selects which profile the MCD 500 will
use for an AAC adaptive acceleration
control soft start. See Starting Modes in
chapter Application Examples for more
details.
Early Acceleration
Constant Acceleration
Late Acceleration
1-14 Adaptive Stop Profile
Option: Function:
Selects which profile the MCD 500 will
use for an AAC adaptive acceleration
control soft stop. See Stopping Modes in
chapter Application Examples for more
details.
Early Deceleration
Constant Deceleration
Late Acceleration
7.4.1 Brake
Brake uses DC injection to actively slow the motor. See
Stopping Modes in chapter Application Examples for more
details.
1-15 Brake Torque
Range: Function:
20%* [20 - 100%] Sets the amount of brake torque the MCD 500
will use to slow the motor.
1-16 Brake Time
Range: Function:
1 sec* [1 - 30 secs] Sets the duration for DC injection during a
braking stop.
NOTE
Parameter 1-16 is used in conjunction
with Par. 1-11. See Brake for details.
7.5 Protection
2-1 Phase Sequence
Option: Function:
Selects which phase sequences the soft starter
will allow at a start. During its pre-start checks,
the starter examines the sequence of the phases
at its input terminals and trips of the actual
sequence does not match the selected option.
Any sequence
Positive only
Negative only
7.5.1 Current Imbalance
The MCD 500 can be configured to trip if the currents on the
three phases vary from each other by more than a specified
amount. The imbalance is calculated as the difference
between the highest and lowest currents on all three phases,
as a percentage of the highest current.
Current imbalance detection is desensitised by 50% during
starting and soft stopping.
2-2 Current Imbalance
Range: Function:
30%* [10% - 50%] Sets the trip point for current imbalance
protection.
2-3 Current Imbalance Delay
Range: Function:
3 secs* [0:00 - 4:00
(min:secs)]
Slows the MCD 500's response to
current imbalance, avoiding trips
due to momentary fluctuations.
7.5.2 Undercurrent
The MCD 500 can be configured to trip if the average current
of all three phases drops below a specified level while the
motor is running.
Programming MCD 500 Operating Instruction
52 MG.17.K3.02 - VLT
®
is a registered Danfoss trademark
77